H07Z1-U Power Cord for Subway System

Maximum temperature range during operation : 70°C
Maximum short circuit temperature (5 Seconds) : 160°C
Minimum bending radius :
OD<8mm : 4 × Overall Diameter
8mm≤OD≤12mm : 5 × Overall Diameter
OD>12mm : 6 × Overall Diameter


Product Detail

Product Tags

CABLE CONSTRUCTION

Conductor : Copper conductor according to BS EN 60228 class 1/2/5.

H07Z1-U : 1.5-10mm2 Class 1 solid copper conductor to BS EN 60228.

Insulation : Thermoplastic compound of type TI 7 to EN 50363-7.

Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

H07Z1-U is a single-core cable with solid or stranded copper wires as conductors.

It is designed to comply with European standards and is suitable for circuits with AC voltages up to 1000V or DC voltages of 750V.

The conductor has a maximum operating temperature of 90°C, ensuring stable performance in high temperature environments.

The insulation is low smoke and non-halogen (LSZH), which increases safety in case of fire and reduces the production of toxic fumes.

COLOUR CODE

Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 70°C
Maximum short circuit temperature (5 Seconds) : 160°C
Minimum bending radius :
OD<8mm : 4 × Overall Diameter
8mm≤OD≤12mm : 5 × Overall Diameter
OD>12mm : 6 × Overall Diameter

 

FEATURES

Low smoke and halogen free: in case of fire, it releases less smoke and is halogen free, which reduces the harm to human body and environment.

High temperature resistance: can work continuously under 90°C, suitable for installation inside equipment with high temperature.

Flame retardant: Comply with EC60332-1-2 and other standards, with good flame retardant and self-extinguishing characteristics to improve safety.

Environmental protection certification: such as ROHS certification, indicating that its materials are environmentally friendly and do not contain harmful substances.

Internal wiring: suitable for wiring inside switches, patch panels and electrical equipment, emphasizing its suitability for applications with high precision or safety requirements.

APPLICATION

Public buildings: Due to its low-smoke and halogen-free characteristics, it is particularly suitable for installation in public and government buildings, such as hospitals, schools, office buildings, etc., to protect personnel safety.

Inside electrical equipment: Used for internal wiring of electrical and electronic equipment, especially in environments where there may be increased danger due to smoke or toxic fumes.

Duct wiring: Commonly used for fixed laying in ducts, suitable for occasions where hidden wiring is required.

High safety standard areas: in places where there are strict requirements for fire protection and environmental performance of cables, such as data centers and subway systems.

In summary, H07Z1-U power cables are widely used in electrical installations that require high safety and low environmental impact due to their safety, environmental protection and high temperature resistance properties

 

CONSTRUCTION PARAMETERS

Conductor

FTX100 07Z1-U/R/K

No. of Cores × Cross-sectional Area

Conductor Class

Nominal Insulation Thickness

Min. Overall Diameter

Max. Overall Diameter

Approx. Weight

No.×mm²

mm

mm

mm

kg/km

1×1.5

1

0.7

2.6

3.2

22

1×2.5

1

0.8

3.2

3.9

35

1×4

1

0.8

3.6

4.4

52

1×6

1

0.8

4.1

5

73

1×10

1

1

5.3

6.4

122

1×1.5

2

0.7

2.7

3.3

24

1×2.5

2

0.8

3.3

4

37

1×4

2

0.8

3.8

4.6

54

1×6

2

0.8

4.3

5.2

76

1×10

2

1

5.6

6.7

127

1×16

2

1

6.4

7.8

191

1×25

2

1.2

8.1

9.7

301

1×35

2

1.2

9

10.9

405

1×50

2

1.4

10.6

12.8

550

1×70

2

1.4

12.1

14.6

774

1×95

2

1.6

14.1

17.1

1069

1×120

2

1.6

15.6

18.8

1333

1×150

2

1.8

17.3

20.9

1640

1×185

2

2

19.3

23.3

2055

1×240

2

2.2

22

26.6

2690

1×300

2

2.4

24.5

29.6

3364

1×400

2

2.6

27.5

33.2

4252

1×500

2

2.8

30.5

36.9

5343

1×630

2

2.8

34

41.1

6868

1×1.5

5

0.7

2.8

3.4

23

1×2.5

5

0.8

3.4

4.1

37

1×4

5

0.8

3.9

4.8

54

1×6

5

0.8

4.4

5.3

76

1×10

5

1

5.7

6.8

128

1×16

5

1

6.7

8.1

191

1×25

5

1.2

8.4

10.2

297

1×35

5

1.2

9.7

11.7

403

1×50

5

1.4

11.5

13.9

577

1×70

5

1.4

13.2

16

803

1×95

5

1.6

15.1

18.2

1066

1×120

5

1.6

16.7

20.2

1332

1×150

5

1.8

18.6

22.5

1660

1×185

5

2

20.6

24.9

2030

1×240

5

2.2

23.5

28.4

2659

ELECTRICAL PROPERTIES

Conductor operating temperature : 70°C

Ambient temperature : 30°C

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4D1A

Conductor cross-sectional area

Ref. Method A (enclosed in conduit in thermally insulating wall etc.)

Ref. Method B (enclosed in conduit on a wall or in trunking etc.)

Ref. Method C (clipped direct)

Ref. Method F (in free air or on a perforated cable tray horizontal or vertical)

Touching

Spaced by one diameter

2 cables, single-phase a.c. or d.c.

3 or 4 cables, three-phase a.c.

2 cables, single-phase a.c. or d.c

3 or 4 cables, three-phase a.c.

2 cables, single-phase a.c. or d.c. flat and touching

3 or 4 cables, three-phase a.c. flat and touching or trefoil

2 cables, single-phase a.c. or d.c. flat

3 cables, three-phase a.c. flat

3 cables, three-phase a.c. trefoil

2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c. flat

Horizontal

Vertical

1

2

3

4

5

6

7

8

9

10

11

12

mm2

A

A

A

A

A

A

A

A

A

A

A

1.5

14.5

13.5

17.5

15.5

20

18

-

-

-

-

-

2.5

20

18

24

21

27

25

-

-

-

-

-

4

26

24

32

28

37

33

-

-

-

-

-

6

34

31

41

36

47

43

-

-

-

-

-

10

46

42

57

50

65

59

-

-

-

-

-

16

61

56

76

68

87

79

-

-

-

-

-

25

80

73

101

89

114

104

131

114

110

146

130

35

99

89

125

110

141

129

162

143

137

181

162

50

119

108

151

134

182

167

196

174

167

219

197

70

151

136

192

171

234

214

251

225

216

281

254

95

182

164

232

207

284

261

304

275

264

341

311

120

210

188

269

239

330

303

352

321

308

396

362

150

240

216

300

262

381

349

406

372

356

456

419

185

273

245

341

296

436

400

463

427

409

521

480

240

321

286

400

346

515

472

546

507

485

615

569

300

367

328

458

394

594

545

629

587

561

709

659

400

-

-

546

467

694

634

754

689

656

852

795

500

-

-

626

533

792

723

868

789

749

982

920

630

-

-

720

611

904

826

1005

905

855

1138

1070

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4D1B

Conductor cross-sectional area

2 cables d.c.

2 cables, single-phase a.c.

3 or 4 cables, three-phase a.c.

Ref. Methods A&B (enclosed in conduit or trunking)

Ref. Methods C & F(clipped direct,聽on trays or in free air)

Ref. Methods A & B (enclosed in conduit or trunking)

Ref. Methods C & F (clipped direct, on trays or in free air)

Cables touching, Trefoil

Cables touching, flat

Cables spaced*, flat

Cables touching

Cables spaced*

1

2

3

4

5

6

7

8

9

mm2

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

1.5

29

29

29

29

25

25

25

25

2.5

18

18

18

18

15

15

15

15

4

11

11

11

11

9.5

9.5

9,5

9.5

6

7.3

7.3

7.3

7.3

6.4

6.4

6.4

6.4

10

4.4

4.4

4.4

4.4

3.8

3.8

3.8

3.8

16

2.8

2.8

2.8

2.8

2.4

2.4

2.4

2.4

r

x

z

r

x

z

r

x

z

r

x

z

r

x

z

r

x

z

r

x

z

25

1.75

1.8

0.33

1.8

1.75

0.2

1.75

1.75

0.29

1.8

1.5

0.29

1.55

1.5

0.175

1.5

1.5

0.25

1.55

1.5

0.32

1.55

35

1.25

1.3

0.31

1.3

1.25

0.195

1.25

1.25

0.28

1.3

1.1

0.27

1.1

1.1

0.17

1.1

1.1

0.24

1.1

1.1

0.32

1.15

50

0.93

0.95

0.3

1

0.93

0.19

0.95

0.93

0.28

0.97

0.81

0.26

0.85

0.8

0.165

0.82

0.8

0.24

0.84

0.8

0.32

0.86

70

0.63

0.65

0.29

0.72

0.63

0.185

0.66

0.63

0.27

0.69

0.56

0.25

0.61

0.55

0.16

0.57

0.55

0.24

0.6

0.55

0.31

0.63

95

0.46

0.49

0.28

0.56

0.47

0.18

0.5

0.47

0.27

0.54

0.42

0.24

0.48

0.41

0.155

0.43

0.41

0.23

0.47

0.4

0.31

0.51

120

0.36

0.39

0.27

0.47

0.37

0.175

0.41

0.37

0.26

0.45

0.33

0.23

0.41

0.32

0.15

0.36

0.32

0.23

0.4

0.32

0.3

0.44

150

0.29

0.31

0.27

0.41

0.3

0.175

0.34

0.29

0.26

0.39

0.27

0.23

0.36

0.26

0.15

0.3

0.26

0.23

0.34

0.26

0.3

0.4

185

0.23

0.25

0.27

0.37

0.24

0.17

0.29

0.24

0.26

0.35

0.22

0.23

0.32

0.21

0.145

0.26

0.21

0.22

0.31

0.21

0.3

0.36

240

0.18

0.195

0.26

0.33

0.185

0.165

0.25

0.185

0.25

0.31

0.17

0.23

0.29

0.16

0.145

0.22

0.16

0.22

0.27

0.16

0.29

0.34

300

0.145

0.16

0.26

0.31

0.15

0.165

0.22

0.15

0.25

0.29

0.14

0.23

0.27

0.13

0.14

0.19

0.13

0.22

0.25

0.13

0.29

0.32

400

0.105

0.13

0.26

0.29

0.12

0.16

0.2

0.115

0.25

0.27

0.12

0.22

0.25

0.105

0.14

0.175

0.105

0.21

0.24

0.1

0.29

0.31

500

0.086

0.11

0.26

0.28

0.098

0.155

0.185

0.093

0.24

0.26

0.1

0.22

0.25

0.086

0.135

0.16

0.086

0.21

0.23

0.081

0.29

0.3

630

0.068

0.094

0.25

0.27

0.081

0.155

0.175

0.076

0.24

0.25

0.08

0.22

0.24

0.072

0.135

0.15

0.072

0.21

0.22

0.066

0.28

0.29

Note: *Spacings larger than one cable diameter will result in a large voltage drop.

r = conductor resistance at operating temperature

x = reactance

z = impedance