H07Z1-K Electric Wires for Important Data Centers

Maximum temperature range during operation : 70°C
Maximum short circuit temperature (5 Seconds) : 160°C
Minimum bending radius :
OD<8mm : 4 × Overall Diameter
8mm≤OD≤12mm : 5 × Overall Diameter
OD>12mm : 6 × Overall Diameter


Product Detail

Product Tags

CABLE CONSTRUCTION

Conductor : Copper conductor according to BS EN 60228 class 1/2/5.

H07Z1-K : 1.5-240mm2 Class 5 stranded copper conductor to BS EN 60228.

Insulation : Thermoplastic compound of type TI 7 to EN 50363-7.

Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

Voltage Rating: H07Z1-K is normally suitable for 450/750 volt environments.

Insulation: Cross-linked polyolefin or similar materials are used as insulation to ensure electrical performance at high temperatures.

Operating Temperature: The operating temperature range is from -15°C to +90°C in dynamic use, and can withstand temperatures from -40°C to +90°C in static use.

Bending radius: dynamic bending radius of 8 times the cable diameter, the same in static.

Flame retardant: conforms to IEC 60332.1 standard, with certain flame retardant properties.

Specification: According to different conductor cross-sectional area, there are various specifications, such as 1.5mm², 2.5mm², etc., to meet different current carrying requirements.

COLOUR CODE

Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 70°C
Maximum short circuit temperature (5 Seconds) : 160°C
Minimum bending radius :
OD<8mm : 4 × Overall Diameter
8mm≤OD≤12mm : 5 × Overall Diameter
OD>12mm : 6 × Overall Diameter

 

FEATURES

Low smoke and non-halogen: In case of fire, it produces less smoke and does not release toxic gases, which is conducive to the safe evacuation of people.

Heat resistance: can withstand higher temperatures, suitable for long-term work in high-temperature environments.

Insulation performance: good electrical insulation performance, to ensure the safe transmission of electricity.

Flame retardant and safety: Designed to meet fire safety standards, reducing the risk of fire.

Applicable environment: suitable for dry or humid indoor environments, as well as places with strict requirements on smoke and toxicity.

APPLICATION

Indoor Wiring: Widely used for wiring lighting fixtures inside buildings, including residential, commercial and industrial locations.

Valuable equipment: especially suitable for densely populated or areas where valuable equipment is installed, such as high-rise buildings, shopping malls, important data centers, etc., in order to protect the safety of property and personnel.

Electrical connection: It can be used to connect electrical equipment such as lights, switchgear, distribution boxes, etc. to ensure the safe and stable operation of the electrical system.

Industrial environment: due to its good mechanical properties and chemical resistance, it is also suitable for internal wiring or fixed wiring of some industrial equipment.

To summarize, H07Z1-K power cord is particularly suitable for applications requiring high safety standards due to its low-smoke and halogen-free characteristics, ensuring that the hazards are reduced in the event of a fire, as well as good electrical performance and adaptability, and it is widely used in a variety of indoor electrical installations.

 

CONSTRUCTION PARAMETERS

Conductor

FTX100 07Z1-U/R/K

No. of Cores × Cross-sectional Area

Conductor Class

Nominal Insulation Thickness

Min. Overall Diameter

Max. Overall Diameter

Approx. Weight

No.×mm²

mm

mm

mm

kg/km

1×1.5

1

0.7

2.6

3.2

22

1×2.5

1

0.8

3.2

3.9

35

1×4

1

0.8

3.6

4.4

52

1×6

1

0.8

4.1

5

73

1×10

1

1

5.3

6.4

122

1×1.5

2

0.7

2.7

3.3

24

1×2.5

2

0.8

3.3

4

37

1×4

2

0.8

3.8

4.6

54

1×6

2

0.8

4.3

5.2

76

1×10

2

1

5.6

6.7

127

1×16

2

1

6.4

7.8

191

1×25

2

1.2

8.1

9.7

301

1×35

2

1.2

9

10.9

405

1×50

2

1.4

10.6

12.8

550

1×70

2

1.4

12.1

14.6

774

1×95

2

1.6

14.1

17.1

1069

1×120

2

1.6

15.6

18.8

1333

1×150

2

1.8

17.3

20.9

1640

1×185

2

2

19.3

23.3

2055

1×240

2

2.2

22

26.6

2690

1×300

2

2.4

24.5

29.6

3364

1×400

2

2.6

27.5

33.2

4252

1×500

2

2.8

30.5

36.9

5343

1×630

2

2.8

34

41.1

6868

1×1.5

5

0.7

2.8

3.4

23

1×2.5

5

0.8

3.4

4.1

37

1×4

5

0.8

3.9

4.8

54

1×6

5

0.8

4.4

5.3

76

1×10

5

1

5.7

6.8

128

1×16

5

1

6.7

8.1

191

1×25

5

1.2

8.4

10.2

297

1×35

5

1.2

9.7

11.7

403

1×50

5

1.4

11.5

13.9

577

1×70

5

1.4

13.2

16

803

1×95

5

1.6

15.1

18.2

1066

1×120

5

1.6

16.7

20.2

1332

1×150

5

1.8

18.6

22.5

1660

1×185

5

2

20.6

24.9

2030

1×240

5

2.2

23.5

28.4

2659

ELECTRICAL PROPERTIES

Conductor operating temperature : 70°C

Ambient temperature : 30°C

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4D1A

Conductor cross-sectional area

Ref. Method A (enclosed in conduit in thermally insulating wall etc.)

Ref. Method B (enclosed in conduit on a wall or in trunking etc.)

Ref. Method C (clipped direct)

Ref. Method F (in free air or on a perforated cable tray horizontal or vertical)

Touching

Spaced by one diameter

2 cables, single-phase a.c. or d.c.

3 or 4 cables, three-phase a.c.

2 cables, single-phase a.c. or d.c

3 or 4 cables, three-phase a.c.

2 cables, single-phase a.c. or d.c. flat and touching

3 or 4 cables, three-phase a.c. flat and touching or trefoil

2 cables, single-phase a.c. or d.c. flat

3 cables, three-phase a.c. flat

3 cables, three-phase a.c. trefoil

2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c. flat

Horizontal

Vertical

1

2

3

4

5

6

7

8

9

10

11

12

mm2

A

A

A

A

A

A

A

A

A

A

A

1.5

14.5

13.5

17.5

15.5

20

18

-

-

-

-

-

2.5

20

18

24

21

27

25

-

-

-

-

-

4

26

24

32

28

37

33

-

-

-

-

-

6

34

31

41

36

47

43

-

-

-

-

-

10

46

42

57

50

65

59

-

-

-

-

-

16

61

56

76

68

87

79

-

-

-

-

-

25

80

73

101

89

114

104

131

114

110

146

130

35

99

89

125

110

141

129

162

143

137

181

162

50

119

108

151

134

182

167

196

174

167

219

197

70

151

136

192

171

234

214

251

225

216

281

254

95

182

164

232

207

284

261

304

275

264

341

311

120

210

188

269

239

330

303

352

321

308

396

362

150

240

216

300

262

381

349

406

372

356

456

419

185

273

245

341

296

436

400

463

427

409

521

480

240

321

286

400

346

515

472

546

507

485

615

569

300

367

328

458

394

594

545

629

587

561

709

659

400

-

-

546

467

694

634

754

689

656

852

795

500

-

-

626

533

792

723

868

789

749

982

920

630

-

-

720

611

904

826

1005

905

855

1138

1070

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4D1B

Conductor cross-sectional area

2 cables d.c.

2 cables, single-phase a.c.

3 or 4 cables, three-phase a.c.

Ref. Methods A&B (enclosed in conduit or trunking)

Ref. Methods C & F(clipped direct,聽on trays or in free air)

Ref. Methods A & B (enclosed in conduit or trunking)

Ref. Methods C & F (clipped direct, on trays or in free air)

Cables touching, Trefoil

Cables touching, flat

Cables spaced*, flat

Cables touching

Cables spaced*

1

2

3

4

5

6

7

8

9

mm2

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

1.5

29

29

29

29

25

25

25

25

2.5

18

18

18

18

15

15

15

15

4

11

11

11

11

9.5

9.5

9,5

9.5

6

7.3

7.3

7.3

7.3

6.4

6.4

6.4

6.4

10

4.4

4.4

4.4

4.4

3.8

3.8

3.8

3.8

16

2.8

2.8

2.8

2.8

2.4

2.4

2.4

2.4

r

x

z

r

x

z

r

x

z

r

x

z

r

x

z

r

x

z

r

x

z

25

1.75

1.8

0.33

1.8

1.75

0.2

1.75

1.75

0.29

1.8

1.5

0.29

1.55

1.5

0.175

1.5

1.5

0.25

1.55

1.5

0.32

1.55

35

1.25

1.3

0.31

1.3

1.25

0.195

1.25

1.25

0.28

1.3

1.1

0.27

1.1

1.1

0.17

1.1

1.1

0.24

1.1

1.1

0.32

1.15

50

0.93

0.95

0.3

1

0.93

0.19

0.95

0.93

0.28

0.97

0.81

0.26

0.85

0.8

0.165

0.82

0.8

0.24

0.84

0.8

0.32

0.86

70

0.63

0.65

0.29

0.72

0.63

0.185

0.66

0.63

0.27

0.69

0.56

0.25

0.61

0.55

0.16

0.57

0.55

0.24

0.6

0.55

0.31

0.63

95

0.46

0.49

0.28

0.56

0.47

0.18

0.5

0.47

0.27

0.54

0.42

0.24

0.48

0.41

0.155

0.43

0.41

0.23

0.47

0.4

0.31

0.51

120

0.36

0.39

0.27

0.47

0.37

0.175

0.41

0.37

0.26

0.45

0.33

0.23

0.41

0.32

0.15

0.36

0.32

0.23

0.4

0.32

0.3

0.44

150

0.29

0.31

0.27

0.41

0.3

0.175

0.34

0.29

0.26

0.39

0.27

0.23

0.36

0.26

0.15

0.3

0.26

0.23

0.34

0.26

0.3

0.4

185

0.23

0.25

0.27

0.37

0.24

0.17

0.29

0.24

0.26

0.35

0.22

0.23

0.32

0.21

0.145

0.26

0.21

0.22

0.31

0.21

0.3

0.36

240

0.18

0.195

0.26

0.33

0.185

0.165

0.25

0.185

0.25

0.31

0.17

0.23

0.29

0.16

0.145

0.22

0.16

0.22

0.27

0.16

0.29

0.34

300

0.145

0.16

0.26

0.31

0.15

0.165

0.22

0.15

0.25

0.29

0.14

0.23

0.27

0.13

0.14

0.19

0.13

0.22

0.25

0.13

0.29

0.32

400

0.105

0.13

0.26

0.29

0.12

0.16

0.2

0.115

0.25

0.27

0.12

0.22

0.25

0.105

0.14

0.175

0.105

0.21

0.24

0.1

0.29

0.31

500

0.086

0.11

0.26

0.28

0.098

0.155

0.185

0.093

0.24

0.26

0.1

0.22

0.25

0.086

0.135

0.16

0.086

0.21

0.23

0.081

0.29

0.3

630

0.068

0.094

0.25

0.27

0.081

0.155

0.175

0.076

0.24

0.25

0.08

0.22

0.24

0.072

0.135

0.15

0.072

0.21

0.22

0.066

0.28

0.29

Note: *Spacings larger than one cable diameter will result in a large voltage drop.

r = conductor resistance at operating temperature

x = reactance

z = impedance