H05Z1-U/R/K Power Cable for Connecting Sensors Actuators

Maximum temperature range during operation : 70°C
Maximum short circuit temperature (5 Seconds) : 160°C
Minimum bending radius : 4 x Overall Diameter


Product Detail

Product Tags

CABLE CONSTRUCTION

Conductor : Copper conductor according to BS EN 60228 class 1/2/5.
Insulation : Thermoplastic compound of type TI 7 to EN 50363-7.
Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

FIRE PERFORMANCE

Flame Retardance (Single vertical wire or cable test):IEC 60332-1-2; EN 60332-1-2
Reduced Fire Propagation (Vertically-mounted bundled wires & cables test):IEC 60332-3-24; EN 60332-3-24
Halogen Free:IEC 60754-1; EN 50267-2-1
No Corrosive Gas Emission:IEC 60754-2; EN 50267-2-2
Minimum Smoke Emission:IEC 61034-2; EN 61034-2

 

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

Conductor : Copper conductor according to BS EN 60228 class 1/2/5.
Insulation : Thermoplastic compound of type TI 7 to EN 50363-7.
Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 70°C
Maximum short circuit temperature (5 Seconds) : 160°C
Minimum bending radius : 4 x Overall Diameter

COLOUR CODE

Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow. Bi-colours of any combination of the above mono-colours are permitted.

FEATURES

Environmental protection: Due to the use of low-smoke halogen-free insulation materials, the power cord does not produce corrosive gases when burning, which is friendly to electrical equipment and the environment.
Safety: Its low-smoke halogen-free characteristics can improve safety when used in public places (such as government buildings, etc.) where smoke and toxic gases may cause life threats and equipment damage.
Durability: It has good heat resistance and chemical resistance and is suitable for various indoor environments, including dry and humid environments.
Scope of application: It is suitable for the wiring of lighting devices and the wiring of valuable property equipment that must be protected from fire damage.

APPLICATION

Indoor wiring: Power cords are widely used for internal wiring of indoor lighting systems, household appliances, office equipment, etc.
Public places: It is used in the internal wiring of electrical equipment in public places such as government buildings, schools, hospitals, etc., especially in places where personnel safety and equipment protection need to be considered.
Industrial applications: In industrial equipment and control systems, it is used to connect sensors, actuators and other electrical components, especially in environments with high temperatures and special safety requirements.

CONSTRUCTION PARAMETERS

Conductor

FTX100 05Z1-U/R/K

No. of Cores × Cross-sectional Area

Conductor Class

Nominal Insulation Thickness

Min. Overall Diameter

Max. Overall Diameter

Approx. Weight

No.×mm²

mm

mm

mm

kg/km

1×0.50

1

0.6

1.9

2.3

9.4

1×0.75

1

0.6

2.1

2.5

12.2

1×1.0

1

0.6

2.2

2.7

15.4

1×0.50

2

0.6

2

2.4

10.1

1×0.75

2

0.6

2.2

2.6

13

1×1.0

2

0.6

2.3

2.8

16.8

1×0.50

5

0.6

2.1

2.5

9.9

1×0.75

5

0.6

2.2

2.7

13.3

1×1.0

5

0.6

2.4

2.8

16.2

ELECTRICAL PROPERTIES

Conductor operating temperature : 70°C

Ambient temperature : 30°C

Current-Carrying Capacities (Amp)

Conductor Cross-Sectional Area

Single-phase a.c.

Three-phase a.c.

mm2

A

A

0.5

3

3

0.75

6

6

1

10

10

Note: These values apply to the majority of cases. Further information should be sought in unusual cases eg.:
(i) When high ambient temperatures are involved, ie. above 30℃
(ii) Where long lengths are used
(iii) Where ventilation is restricted
(iv) Where the cords are used for other purposes, ego internal wiring of apparatus.

Voltage Drop (Per Amp Per Meter)

nductor cross-sectional area

2 cables d.c.

2 cables, single-phase a.c.

3 or 4 cables, three-phase a.c.

Ref. Methods A&B (enclosed in conduit or trunking)

Ref. Methods C, F&G (clipped direct, on trays or in free air)

Ref. Methods A&B (enclosed in conduit or trunking)

Ref. Methods C, F&G (clipped direct, on trays or in free air)

Cables touching

Cables spaced*

Cables touching, Trefoil

Cables touching, flat

Cables spaced*, flat

1

2

3

4

5

6

7

8

9

mm2

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

0.5

93

93

93

93

80

80

80

80

0.75

62

62

62

62

54

54

54

54

1

46

46

46

46

40

40

40

40

Note: *Spacings larger than one cable diameter will result in a large voltage drop.