H05V2-K Electrical Cable for Electrical Control Signals
Cable Construction
Fine bare copper strands
Strands to VDE-0295 Class-5, IEC 60228 Class-5, BS 6360 cl. 5 and HD 383
Special heat resistant PVC TI3 core insulation to DIN VDE 0281 part 7
Cores to VDE-0293 colors
H05V2-K (20, 18 & 17 AWG)
H07V2-K (16 AWG and Larger)
Rated voltage: 300V/500V
Rated temperature: usually 70°C, also available in 90°C version
Conductor material: Multi-stranded copper conductor in accordance with GB/T 3956 Type 5 (equivalent to IEC60228.5)
Insulation material: polyvinyl chloride mix (PVC)
Cross-sectional area: 0.5mm² to 1.0mm²
Finished OD: range from 2.12mm to 3.66mm depending on cross-sectional area
Test voltage: 2500V for 5 minutes
Maximum operating temperature: 70°C
Minimum operating temperature: -30°C
Technical Characteristics
Working voltage: 300/500v (H05V2-K)
450/750v (H07V2-K)
Test voltage: 2000 volts
Flexing bending radius: 10-15x O
Static bending radius: 10-15 x O
Flexing temperature: +5o C to +90o C
Static temperature: -10o C to +105o C
Short circuit temperature: +160o C
Flame retardant: IEC 60332.1
Insulation resistance: 20 MΩ x km
Standards and certifications for H05V2-K power cords include
HD 21.7 S2
CEI 20-20
CEI 20-52
VDE-0281 Part 7
CE Low Voltage Directives 73/23/EEC and 93/68/EEC
ROHS certification
These standards and certifications ensure that the H05V2-K power cord is compliant in terms of electrical performance, safety and environmental protection.
Features
Flexibility: It has good flexibility and elasticity, suitable for use in occasions that require frequent bending.
Temperature resistance: able to work in a wide range of temperatures, suitable for high temperature environments, such as varnishing machines and drying towers.
Chemical resistance: PVC insulation has a certain degree of chemical resistance.
Low smoke and halogen free: some versions of H05V2-K power cord are made of low smoke and halogen free material, which reduces smoke and toxic gas emission in case of fire.
High strength: It has high mechanical strength and can withstand certain mechanical pressure.
Applications
Internal wiring of electrical equipment: suitable for internal wiring of lighting and heating equipment.
Industrial power distribution field: Widely used in industrial power distribution field, especially suitable for flexible installation places with strict requirements, such as electric control cabinet, distribution box and all kinds of low-voltage electrical equipment.
Mobile electrical appliances and instruments: applicable to the internal and external connecting wires of medium and light mobile electrical appliances, instruments and meters.
Switchgear and motors: for power installation in high temperature environments such as switchgear, motors and transformers.
Signal transmission: It can be used for transmission of power, electrical control signals and switch signals.
Cable Parameter
AWG |
No. of Cores x Nominal Cross Sectional Area |
Nominal Thickness of Insulation |
Nominal Overall Diameter |
Nominal Copper Weight |
Nominal Weight |
|
# x mm^2 |
mm |
mm |
kg/Km |
kg/Km |
H05V2-K |
|||||
20(16/32) |
1 x 0.5 |
0.6 |
2.5 |
4.8 |
8.7 |
18(24/32) |
1 x 0.75 |
0.6 |
2.7 |
7.2 |
11.9 |
17(32/32) |
1 x 1 |
0.6 |
2.8 |
9.6 |
14 |
H07V2-K |
|||||
16(30/30) |
1 x 1.5 |
0,7 |
3.4 |
14.4 |
20 |
14(50/30) |
1 x 2.5 |
0,8 |
4.1 |
24 |
33.3 |
12(56/28) |
1 x 4 |
0,8 |
4.8 |
38 |
48.3 |
10(84/28) |
1 x 6 |
0,8 |
5.3 |
58 |
68.5 |
8(80/26) |
1 x 10 |
1,0 |
6.8 |
96 |
115 |
6(128/26) |
1 x 16 |
1,0 |
8.1 |
154 |
170 |
4(200/26) |
1 x 25 |
1,2 |
10.2 |
240 |
270 |
2(280/26) |
1 x 35 |
1,2 |
11.7 |
336 |
367 |
1(400/26) |
1 x 50 |
1,4 |
13.9 |
480 |
520 |
2/0(356/24) |
1 x 70 |
1,4 |
16 |
672 |
729 |
3/0(485/24) |
1 x 95 |
1,6 |
18.2 |
912 |
962 |
4/0(614/24) |
1 x 120 |
1,6 |
20.2 |
1115 |
1235 |
300 MCM (765/24) |
1 x 150 |
1,8 |
22.5 |
1440 |
1523 |
350 MCM (944/24) |
1 x 185 |
2,0 |
24.9 |
1776 |
1850 |
500MCM(1225/24) |
1 x 240 |
2,2 |
28.4 |
2304 |
2430 |